Tested Switchboard “BLOKSET”

Product our review

• Tested & verified according to IEC 61439 -1,-2
• High power up to 7000 A
• High degree of protection up to IP54
• Modular & open-ended
• High safety & reliability equipment using SCHNEIDER
• ELECTRIC LV protection components & switchgear
• Compact & economic
• Increased resistance to harsh environments
• Minimum downtimes
• Thermal Monitoring
• Access information in real time
• Increased energy efficiency: up to 30% energy saving

TECHNICAL  DATA

Voltage (kV) 
Up to 690 Vac (50/60 Hz)
Main busbar rating 
Up to 7000 A
Distribution busbar rating
 Up to 3200 A
Rated short-time current (lcw) horizontal main busbar
Up to 100 kArms - 1s (peak current lpk up to 220 kApeak)
Vertical distribution busbar
Up to 100 kArms - 1s (peak current lpk up to 220 kApeak)
Conditional short-circuit current (lsc)
 Up to 85 kA
Internal arc withstand current 
100 kA – 0.4 s (IEC TR 61641)
Earthing system
 TT-IT-TNS-TNC100 kA – 0.4 s (IEC TR 61641)

 