Air Insulated Metal Clad Switchgear (AMC) 17.5 KV
General Description:
- Air-insulated Metal Clad (AMC) panels are type-tested,
air-insulated metal clad units that can be assembled
side-by-side. - The standardized AMC switchgear can be
configured according to customer requirements which
allows it to be functionally matched to its application. - Also,the panels can be extended at either side or modified later
after installation. - The AMC switchgear has separate compartments for
busbars, switchgear, cable connections and low voltage
equipment. - This ensures a high degree of reliability.
Main Features:
- High operating reliability
- Simple maintenance and inspection
- Internal arc tested (25kA-31.5kA 1s)
- Mechanical / electrical interlocks to prevent unsafe operations
- VCB, earthing switch position and voltage presence indicators
- Modular design extensible to both sides
- Easy frontal access to install and to test MV cables
- Use of highly recyclable materials
- Easy cable connection
- Possible to be connected with any SCADA system

Approval:
12KV AMC panel passed all necessary tests carried out in The Egyptian Electricity Authority Pyramids High Voltage Research Center and approved from The Egyptian Electricity Holding Company.
Standards:
The AMC is designed, manufactured and tested in conformity to the latest standards.
IEC publication 60282-1
IEC publication 60529
IEC publication 61243-5
IEC publication 62271-200
IEC publication 62271-1
IEC publication 62271-100
IEC publication 62271-102

TECHNICAL DATA | ||||
---|---|---|---|---|
Electrical Characteristics | IEC | |||
Rated Voltage | 7.5 | 12 | 17.5 | |
Rated Frequency | HZ | 50/60 | ||
Rated normal current | - | |||
A | 630 | |||
A | 1250 | |||
Main Busbars | A | 1600 | ||
A | 2000 | |||
A | 2500 | |||
A | 630 | |||
A | 1250 | |||
Outgoing Busbars | A | 1600 | ||
A | 2000 | |||
A | 2500 | |||
Rated short-time withstand current | - | |||
KA | 16 | |||
With tk = 3 s | KA | 20 | ||
KA | 25 | |||
KA | 31.5 | |||
KA | 40 | |||
Peak value | KA | 50 | ||
KA | 63 | |||
K | 80 | |||
Rated insulation level | - | |||
Rated power-frequency withstand voltage | KV | 20 | 28 | 38 |
Rated lightning impulse withstand voltage | KV | 60 | 75 | 95 |
Internal arc classification according to IEC 62271-200 | AFL | 25 KA / 31.5 KA 1 s | ||
Degree of protection (Enclosure) | IP | IP 4X | ||
Colour of equipment (Standard) | RAL | RAL 7035 (*) | ||
Loss of service continuity category | LSC | LSC2B | ||
Partition class | PM |